Single Core Cable - Multi Stranded

Code: H05V-K  H07V-K | 2491X

Construction

  1. Finely stranded copper conductor
  2. PVC insulation

Standard

  • BS 6004
  • TS 9758 HD 21.3 S3

Application

  • Domestic and light industrial wiring.
  • Can be clipped to surface, on trays or in free air where there is little risk of mechanical damage.
  • Suitable for laying into trunking or conduit etc. when mechanical protection is required.
  • May be embedded in plaster.

Voltage

  • Rated Voltage: Uo/U = 300/500V - 450/750 V
  • AC test voltage: 2 kV - 2.5kV

Technical Data

  • Maximum operating temperature 70°C
  • Short-circuit temperature 160°C
  • Current carrying capacity values given below are rated at 30°C ambient temperature
Type Nomimal cross section Conductor Insulation Thickness Overall diameter approx. Net weight approx. Standard delivery length Type packing, coil or drum size Conductor DC resistance at 20°c max. Current carrying capacity
Conduit On Air
  mm³ mm mm kg/km m cm Ohm/km
H05V-K 0,5 0,6 2,2 9 100 Coil 39    
H05V-K 0,75 0,6 2,4 12 100 Coil 26   16
H05V-K 1 0,6 2,6 14 100 Coil 19,5 12 20
H07V-K 1,5 0,7 3,0 20 100 Coil 13,3 16 24
H07V-K 2,5 0,8 3,7 31 100 Coil 7,98 20 32
H07V-K 4 0,8 4,2 46 100 Coil 4,95 26 42
H07V-K 6 0,8 4,7 63 100 Coil 3,3 34 54
H07V-K 10 1,0 6,0 110 100 Coil 1,91 46 74
H07V-K 16 1,0 7,2 160 100 Coil 1,21 61 98
H07V-K 25 1,2 9,0 252 100 Coil 0,78 82 130
H07V-K 35 1,2 10,0 332 100 Coil 0,554 100 158
H07V-K 50 1,4 12,2 542 1000 80 0,286 120 198
H07V-K 70 1,4 14,0 650 1000 80 0,272 152 245
H07V-K 95 1,6 16,0 862 1000 100 0,206 184 292
H07V-K 120 1,6 18,0 1080 1000 100 0,161 212 344
H07V-K 150 1,8 22,0 1480 1000 120 0,129 - 390
H07V-K 185 2,0 24,0 1840 1000 120 0,106 - 448
H07V-K 240 2,2 28,0 2460 1000 140 0,0801 - 530