Circular Multi Core Cable

Code: H05VV-7 | 318_Y

Construction

  1. Finely stranded copper conductor
  2. PVC insulation
  3. PVC outer sheath
Standard
  • BS 6500
  • TS 9760 HD 21.5 S3
Application
  • Used in dry and humid places, as connecting cable with low mechanical stress and generally for household appliances .
Voltage
  • Rated Voltage: Uo/U = 300/500V
  • AC test voltage: 2 kV
Technical Data
  • Maximum operating temperature 70°C
  • Short-circuit temperature 160°C
  • Current carrying capacity values given below are rated at 30°C ambient temperature
Nomimal cross section Conductor insulation thickness Sheath thickness  Overall diameter approx. Net weight approx. Standard delivery length Type packing, coil or drum size Conductor DC resistance at 20°c max. Current carrying capacity in air
mm³ mm mm mm kg/km m cm Ohm/km
2x0,75 0,6 0,8 6,4 60 100 Coil 26 8
2x1 0,6 0,8 6,8 68 100 Coil 19,5 12
2x1,5 0,7 0,8 7,6 88 100 Coil 13,3 18
2x2,5 0,8 1,0 9,3 135 100 Coil 7,98 26
2x4 0,8 1,1 11,0 185 100 Coil 4,95 32
3x0,75 0,6 0,8 6,8 70 100 Coil 26 8
3x1 0,6 0,8 7,1 80 100 Coil 19,5 12
3x1,5 0,7 0,9 8,3 110 100 Coil 13,3 18
3x2,5 0,8 1,1 10,1 168 100 Coil 7,98 26
3x4 0,8 1,2 11,5 230 100 Coil 4,95 32
4x0,75 0,6 0,8 7,4 85 100 Coil 26 8
4x1 0,6 0,9 8,0 102 100 Coil 19,5 12
4x1,5 0,7 1,0 9,3 140 100 Coil 13,3 18
4x2,5 0,8 1,1 11,0 208 100 Coil 7,98 26
4x4 0,8 1,2 12,5 286 100 Coil 4,95 32
5x0,75 0,6 0,9 8,0 100 100 Coil 26 8
5x1 0,6 0,9 8,7 121 100 Coil 19,5 12
5x1,5 0,7 1,1 10,5 170 100 Coil 13,3 18
5x2,5 0,8 1,2 12,0 251 100 Coil 7,98 26