Circular Multi Core Cable with Filler

Code: NYM

Construction
  1. Solid or stranded copper conductor
  2. PVC insulation
  3. PVC outer sheath
  4. Filler
Standard:
  • VDE 0250 Part 204 HD 21.4.S2
Application
  • Used in dry and humid places where there is no mechanical stress and in all kinds of building embedded in or above plaster. 
  • Not suitable to be layed underground
Voltage
  • Rated Voltage: Uo/U = 300/500V
  • AC test voltage: 2 kV
Technical Data
  • Maximum operating temperature 70°C
  • Short-circuit temperature 160°C
  • Current carrying capacity values given below are rated at 30°C ambient temperature

Nomimal cross section Conductor insulation thickness Sheath thickness  Overall diameter approx. Net weight approx. Standard delivery length Type packing, coil or drum size Conductor DC resistance at 20°c max. Current carrying capacity in air
mm²   mm mm mm kg/km m cm Ohm/km
2x1,5 re 0,7 1,2 8,7 114 100 Coil 12,1 19
2x2,5 re 0,8 1,2 10,0 155 100 Coil 7,41 26
2x4 re 0,8 1,2 11,0 200 100 Coil 4,61 35
2x6 re 0,8 1,2 12,0 260 100 Coil 3,08 45
2x10 rm 1,0 1,4 15,6 440 1000 100 1,83 62
2x16 rm 1,0 1,6 17,8 610 1000 120 1,15 84
2x25 rm 1,2 1,4 22,0 910 1000 120 0,727 110
3x1,5 re 0,7 1,2 9,3 135 100 Coil 12,1 19
3x2,5 re 0,8 1,2 10,5 190 100 Coil 7,41 26
3x4 re 0,8 1,2 11,6 250 100 Coil 4,61 35
3x6 re 0,8 1,4 13,5 335 100 Coil 3,08 45
3x10 rm 1,0 1,4 16,8 555 1000 120 1,83 62
3x16 rm 1,0 1,4 20,0 800 1000 140 1,15 84
3x25 rm 1,2 1,6 24,0 1.2 1000 160 0,727 110
4x1,5 re 0,7 1,2 10,0 160 100 Coil 12,1 19
4x2,5 re 0,8 1,2 11,3 230 100 Coil 7,41 26
4x4 re 0,8 1,4 13,0 310 100 Coil 4,61 35
4x6 re 0,8 1,4 14,5 420 100 Coil 3,08 45
4x10 rm 1,0 1,4 18,0 675 1000 120 1,83 62
4x16 rm 1,0 1,4 21 980 1000 140 1,15 84
4x25 rm 1,2 1,6 26 1.5 1000 160 0,727 110