Code: N2XY
Construction
- Copper conductor
- XLPE insulat
- PVC outer sheath
Standard: IEC 60502 - 1
Application
- This type of cable can be used as an energy, network and illumination cable for domestic and industrial use, indoors and outdoors, as well as for energy distribution to the network, underground and cable channel.
Voltage
- Rated Voltage: Uo/U = 0.6/1 kV
- AC test voltage: 3.5 kV
Technical Data
- Maximum operating temperature 90°C
- Short-circuit temperature 250°C
- Current carrying capacity values given below are rated at 20°C earth temperature, at 30ºC free air temperature, 1 K.m/W and 0.7 charging conditions.
Nomimal cross section | Conductor insulation thickness | Sheat thickness | Overall diameter approx. | Net weight approx. | Standard delivery length | Type packing, coil or drum size | Conductor DC resistance at 20°c max. | Current carrying capacity | ||||
mm² | mm | mm | mm | kg/km | m | cm | Ohm/km | A | A | A | A | |
1x4 | re | 0,7 | 1,4 | 6,5 | 75 | 1000 | 80 | 4,61 | - | 45 | 37 | |
1x6 | re | 0,7 | 1,4 | 7,2 | 98 | 1000 | 80 | 3,08 | - | 57 | 48 | |
1x10 | rm | 0,7 | 1,4 | 8,1 | 140 | 1000 | 80 | 1,83 | - | 78 | 66 | |
1x16 | rm | 0,7 | 1,4 | 9,2 | 200 | 1000 | 80 | 1,15 | 127 | 107 | 103 | 89 |
1x25 | rm | 0,9 | 1,4 | 10,9 | 297 | 1000 | 90 | 0,727 | 163 | 137 | 137 | 118 |
1x35 | rm | 0,9 | 1,4 | 12,0 | 400 | 1000 | 90 | 0,524 | 195 | 165 | 169 | 145 |
1x50 | rm | 1,0 | 1,4 | 13,4 | 520 | 1000 | 100 | 0,387 | 230 | 195 | 206 | 176 |
1x70 | rm | 1,1 | 1,5 | 16,0 | 785 | 1000 | 100 | 0,268 | 282 | 239 | 261 | 224 |
1x95 | rm | 1,1 | 1,5 | 17,5 | 990 | 1000 | 120 | 0,193 | 336 | 287 | 321 | 271 |
1x120 | rm | 1,2 | 1,6 | 19,6 | 1280 | 1000 | 120 | 0,153 | 382 | 326 | 374 | 314 |
1x150 | rm | 1,4 | 1,6 | 21,0 | 1470 | 1000 | 140 | 0,124 | 428 | 366 | 428 | 361 |
1x185 | rm | 1,6 | 1,7 | 24,0 | 1880 | 1000 | 140 | 0,0991 | 483 | 414 | 494 | 412 |
1x240 | rm | 1,7 | 1,8 | 26,3 | 2380 | 1000 | 160 | 0,0754 | 561 | 481 | 590 | 484 |