Single Core XLPE Insulated Cable

Code: N2XY

Construction

  1. Copper conductor
  2. XLPE insulat
  3. PVC outer sheath
Standard: IEC 60502 - 1
Application
  • This type of cable can be used as an energy, network and illumination cable for domestic and industrial use, indoors and outdoors, as well as for energy distribution to the network, underground and cable channel.
Voltage
  • Rated Voltage: Uo/U = 0.6/1 kV
  • AC test voltage: 3.5 kV
Technical Data
  • Maximum operating temperature 90°C
  • Short-circuit temperature 250°C
  • Current carrying capacity values given below are rated at 20°C earth temperature, at 30ºC free air temperature, 1 K.m/W and 0.7 charging conditions.

Nomimal cross section Conductor insulation thickness Sheat thickness  Overall diameter approx. Net weight approx. Standard delivery length Type packing, coil or drum size Conductor DC resistance at 20°c max. Current carrying capacity
mm²   mm mm mm kg/km m cm Ohm/km
1x4 re 0,7 1,4 6,5 75 1000 80 4,61 -   45 37
1x6 re 0,7 1,4 7,2 98 1000 80 3,08 -   57 48
1x10 rm 0,7 1,4 8,1 140 1000 80 1,83 -   78 66
1x16 rm 0,7 1,4 9,2 200 1000 80 1,15 127 107 103 89
1x25 rm 0,9 1,4 10,9 297 1000 90 0,727 163 137 137 118
1x35 rm 0,9 1,4 12,0 400 1000 90 0,524 195 165 169 145
1x50 rm 1,0 1,4 13,4 520 1000 100 0,387 230 195 206 176
1x70 rm 1,1 1,5 16,0 785 1000 100 0,268 282 239 261 224
1x95 rm 1,1 1,5 17,5 990 1000 120 0,193 336 287 321 271
1x120 rm 1,2 1,6 19,6 1280 1000 120 0,153 382 326 374 314
1x150 rm 1,4 1,6 21,0 1470 1000 140 0,124 428 366 428 361
1x185 rm 1,6 1,7 24,0 1880 1000 140 0,0991 483 414 494 412
1x240 rm 1,7 1,8 26,3 2380 1000 160 0,0754 561 481 590 484