XLPE Insulated Low Voltage Cable

Code: N2XY

Construction
  1. Copper conducto
  2. XLPE insulation
  3. PVC outer sheath
  4. Filler
Standard
  • IEC 60502 -1       

Application

  • This type of cable can be used as an energy, network and illumination cable for domestic and industrial use, indoors and outdoors, as well as for energy distribution to the network, underground and cable channel.

Voltage

  • Rated Voltage:    Uo/U = 0.6/1 kV
  • AC test voltage:    3.5 kV        

Technical Data

  • Maximum operating temperature 90°C
  • Short-circuit temperature 250°C
  • Current carrying capacity values given below are rated at 20°C earth temperature, at 30ºC free air temperature, 1 K.m/W and 0.7 charging conditions.
Nomimal cross section Conductor insulation thickness Sheat thickness Overall diameter approx. Net weight approx. Standard delivery length Type packing, coil or drum size Conductor DC resistance at 20°c max. Current carrying capacity
mm²   mm mm mm kg/km m cm Ohm/km
5x1,5 re 0,7 1,8 13,0 230 1 80 12,1 24 18
7x1,5 re 0,7 1,8 14,0 280 1 100 12,1 15 12
10x1,5 re 0,7 1,8 16,0 340 1 100 12,1 12 10
12x1,5 re 0,7 1,8 16,5 280 1 100 12,1 12 9
14x1,5 re 0,7 1,8 17,0 430 1 100 12,1 11 9
19x1,5 re 0,8 1,8 19,0 540 1 120 12,1 10 8
21x1,5 re 0,7 1,8 20,0 590 1 120 12,1 9 8
24x1,5 re 0,7 1,8 22,0 680 1 130 12,1 8 7
30x1,5 re 0,7 1,8 23,0 810 1 140 12,1 8 7
40x1,5 re 0,7 1,8 26,0 1.05 1 160 12,1 7 6
5x2,5 re 0,7 1,8 14,0 300 1 100 7,41 34 25
7x2,5 re 0,7 1,8 15,0 337 1 100 7,41 20 16
10x2,5 re 0,7 1,8 17,5 460 1 120 7,41 17 14
12x2,5 re 0,7 1,8 18,0 520 1 120 7,41 16 13
14x2,5 re 0,7 1,8 19,0 590 1 120 7,41 15 12
19x2,5 re 0,7 1,8 21,0 770 1 130 7,41 14 11
21x2,5 re 0,7 1,8 22,0 840 1 140 7,41 12 10
24x2,5 re 0,7 1,8 24,0 950 1 150 7,41 12 10
30x2,5 re 0,7 1,8 26,0 1.16 1 150 7,41 11 9
40x2,5 re 0,7 1,9 29,0 1.75 1 160 7,41 11 9