Code: YXZ2V
Construction- Copper conductor
- XLPE insulation
- Filler
- Separation sheath
- Galvanized round steel wire armouring
- Galvanized steel tape
- PVC outer sheath
Standard
- BS 5467
- IEC 60502
- TS IEC 60502 - 1
Application
- Mainly used in populated areas, power and switching stations underground.
- Steel wire protects the cable from any mechanical damage.
Voltage
- Rated Voltage: Uo/U = 0.6/1 kV
- AC test voltage: 3.5 kV
Technical Data
- Maximum operating temperature 90°C
- Short-circuit temperature 250°C
- Current carrying capacity values given below are rated at 20°C earth temperature, at 30ºC free air temperature, 1 K.m/W and 0.7 charging conditions
Nomimal cross section | Conductor insulation thickness | Sheath thickness | Overall diameter approx. | Net weight approx. | Standard delivery length | Type packing, coil or drum size | Conductor DC resistance at 20°c max. | Current carrying capacity | ||
mm² | mm | mm | mm | kg/km | m | cm | Ohm/km | A | A | |
3x1,5 | re | 0,7 | 1,8 | 14,0 | 360 | 1000 | 100 | 12,1 | 26 | 18 |
3x2,5 | re | 0,7 | 1,8 | 15,0 | 450 | 1000 | 100 | 7,41 | 34 | 25 |
3x4 | re | 0,7 | 1,8 | 17,0 | 660 | 1000 | 110 | 4,61 | 44 | 34 |
3x6 | re | 0,7 | 1,8 | 19,0 | 760 | 1000 | 120 | 3,08 | 56 | 43 |
3x10 | rm | 0,7 | 1,8 | 21,0 | 960 | 1000 | 120 | 1,83 | 75 | 60 |
3x16 | rm | 0,7 | 1,8 | 22,0 | 1210 | 1000 | 130 | 1,15 | 98 | 80 |
4x1,5 | re | 0,7 | 1,8 | 15,0 | 420 | 500 | 100 | 12,1 | 26 | 18 |
4x2,5 | re | 0,7 | 1,8 | 17,0 | 610 | 500 | 110 | 7,41 | 34 | 25 |
4x4 | re | 0,7 | 1,8 | 19,0 | 750 | 500 | 120 | 4,61 | 44 | 34 |
4x6 | re | 0,7 | 1,8 | 20,0 | 875 | 500 | 120 | 3,08 | 56 | 43 |
4x10 | rm | 0,7 | 1,8 | 22,0 | 1135 | 250 | 130 | 1,83 | 75 | 60 |