Single Core PVC Insulated Low Voltage Cable

Code: NYY

Construction                                

  • Copper conductor
  • PVC insulation
  • PVC outer sheath                       

Standard

  • IEC 60502 - 1

Application

  • Used as energy, network and illumination cable.
  • Does not take stress.

Voltage

  • Rated Voltage:    Uo/U = 0.6/1 kV
  • AC test voltage:    3.5 kV                             

Technical Data

  • Maximum operating temperature 70°C
  • Short-circuit temperature 160°C
  • Current carrying capacity values given below are rated at 20°C earth temperature, at 30ºC free air temperature, 1 K.m/W and 0.7 charging conditions.
Nomimal cross section Conductor insulation thickness Sheath thickness  Overall diameter approx. Net weight approx. Standard delivery length Type packing, coil or drum size  Conductor DC resistance at 20°c max. Current carrying capacity
mm²   mm mm mm kg/km m cm Ohm/km
1x4 re 1,0 1,4 8,0 90 1000 80 4,61 -   45 37
1x6 re 1,0 1,4 8,5 110 1000 80 3,08 -   57 48
1x10 rm 1,0 1,4 8,6 160 1000 80 1,83 -   78 66
1x16 rm 1,0 1,4 10,8 230 1000 80 1,15 127 107 103 89
1x25 rm 1,2 1,4 12,5 330 1000 90 0,727 163 137 137 118
1x35 rm 1,2 1,4 13,5 440 1000 90 0,524 195 165 169 145
1x50 rm 1,4 1,4 14,5 570 1000 100 0,387 230 195 206 176
1x70 rm 1,4 1,5 16,5 830 1000 100 0,268 282 239 261 224
1x95 rm 1,6 1,5 18,5 1060 1000 120 0,193 336 287 321 271
1x120 rm 1,2 1,6 21,0 1340 1000 120 0,153 382 326 374 314
1x150 rm 1,8 1,6 22,0 1560 1000 140 0,124 428 366 428 361
1x185 rm 2,0 1,7 25,0 1980 1000 140 0,0991 483 414 494 412
1x240 rm 2,2 1,8 28,0 2500 1000 160 0,0754 561 481 590 484