Multi Core PVC Insulated Control Cable

Code: NYY

Construction

  1. Copper conductor
  2. PVC insulation
  3. Filler
  4. PVC outer sheath                               

Code: NYY                           
                               
Standard

  • IEC 60502 - 1                           

Application

  • Used as energy, network and illumination cable.
  • Used in places where there is no mechanical stress                               

Voltage

  • Rated Voltage:    Uo/U = 0.6/1 kV
  • AC test voltage:    3.5 kV                            

Technical Data

  • Maximum operating temperature 70°C
  • Short-circuit temperature 160°C
  • Current carrying capacity values given below are rated at 20°C earth temperature, at 30ºC free air temperature, 1 K.m/W and 0.7 charging conditions
Nomimal cross section Conductor insulation thickness Sheath thickness Overall diameter approx. Net weight approx. Standard delivery length Type packing, coil or drum size Conductor DC resistance at 20°c max. Current carrying capacity
mm²   mm mm mm kg/km mm cm Ohm/km
5x1,5 re 0,8 1,8 14,0 280 1 90 12,1 24 18
7x1,5 re 0,8 1,8 15,0 330 1 100 12,1 15 12
10x1,5 re 0,8 1,8 17,4 475 1 110 12,1 12 10
12x1,5 re 0,8 1,8 18,0 520 1 110 12,1 12 9
14x1,5 re 0,8 1,8 19,0 570 1 120 12,1 11 9
19x1,5 re 0,8 1,8 20,0 710 1 120 12,1 10 8
21x1,5 re 0,8 1,8 21,0 780 1 120 12,1 9 8
24x1,5 re 0,8 1,8 23,0 920 1 130 12,1 8 7
30x1,5 re 0,8 1,8 25,0 1.06 1 140 12,1 8 7
40x1,5 re 0,8 1,8 28,0 1.34 1 150 12,1 7 6
5x2,5 re 0,8 1,8 15,0 350 1 100 7,41 34 25
7x2,5 re 0,8 1,8 16,0 420 1 110 7,41 20 16
10x2,5 re 0,8 1,8 19,0 620 1 120 7,41 17 14
12x2,5 re 0,8 1,8 19,5 675 1 120 7,41 16 13
14x2,5 re 0,8 1,8 21,0 750 1 120 7,41 15 12
19x2,5 re 0,8 1,8 23,0 945 1 130 7,41 14 11
21x2,5 re 0,8 1,8 24,0 1.04 1 140 7,41 12 10
24x2,5 re 0,8 1,8 26,0 1.23 1 150 7,41 12 10
30x2,5 re 0,8 1,8 27,0 1.42 1 150 7,41 11 9
40x2,5 re 0,8 1,9 30,3 1.83 1 160 7,41 11 9