Single and Multi Core Halogen Free Cable - 1

Code: NHXMH

Construction

  • Copper conductor
  • HX insulation
  • Special filler
  • Special outer sheath                                               

Standard:

  • VDE 0250 part 214                            

Application

  • Used in densely populated areas, multi storey buildings, hospitals, shopping centres and data information centres since, in case of fire, it is toxic free.

Voltage

  • Rated Voltage:    Uo/U = 300/500 V
  • AC test voltage:    2 kV                             

Technical Data

  • Maximum operating temperature 70°C
  • Short-circuit temperature 160°C
  • Current carrying capacity values given below are rated at 30°C ambient temperature 
Nomimal cross section Overall diameter approx. Net weight approx. Standard delivery length Type packing, coil or drum size Conductor DC resistance at 20°c max. Current carrying capacity in air
mm²   mm kg/km m cm Ohm/km
1 x 1,5 re 5,2 43 1000 70 12,1 24
1 x 2,5 re 5,6 51 1000 70 7,41 32
1 x 4 re 6,3 73 1000 70 4,61 42
1 x 6 re 6,8 94 1000 70 3,08 54
1 x 10 rm 7,8 140 1000 70 1,83 73
1 x 16 rm 9,4 205 1000 70 1,15 98
2 x 1,5 rm 8,4 106 1000 70 12,1 24
2 x 2,5 re 9,6 140 1000 70 7,41 32
2 x 4 re 10,3 190 1000 80 4,61 42
2 x 6 re 11,6 245 1000 90 3,08 54
2 x 10 rm 14,7 390 1000 100 1,83 73
2 x 16 rm 17,2 550 1000 110 1,15 98