Code: NHXMH
Construction
- Copper conductor
- HX insulation
- Special filler
- Special outer sheath
Standard:
- VDE 0250 part 214
Application
- Used in densely populated areas, multi storey buildings, hospitals, shopping centres and data information centres since, in case of fire, it is toxic free.
Voltage
- Rated Voltage: Uo/U = 300/500 V
- AC test voltage: 2 kV
Technical Data
- Maximum operating temperature 70°C
- Short-circuit temperature 160°C
- Current carrying capacity values given below are rated at 30°C ambient temperature
Nomimal cross section | Overall diameter approx. | Net weight approx. | Standard delivery length | Type packing, coil or drum size | Conductor DC resistance at 20°c max. | Current carrying capacity in air | |
mm² | mm | kg/km | m | cm | Ohm/km | A | |
1 x 1,5 | re | 5,2 | 43 | 1000 | 70 | 12,1 | 24 |
1 x 2,5 | re | 5,6 | 51 | 1000 | 70 | 7,41 | 32 |
1 x 4 | re | 6,3 | 73 | 1000 | 70 | 4,61 | 42 |
1 x 6 | re | 6,8 | 94 | 1000 | 70 | 3,08 | 54 |
1 x 10 | rm | 7,8 | 140 | 1000 | 70 | 1,83 | 73 |
1 x 16 | rm | 9,4 | 205 | 1000 | 70 | 1,15 | 98 |
2 x 1,5 | rm | 8,4 | 106 | 1000 | 70 | 12,1 | 24 |
2 x 2,5 | re | 9,6 | 140 | 1000 | 70 | 7,41 | 32 |
2 x 4 | re | 10,3 | 190 | 1000 | 80 | 4,61 | 42 |
2 x 6 | re | 11,6 | 245 | 1000 | 90 | 3,08 | 54 |
2 x 10 | rm | 14,7 | 390 | 1000 | 100 | 1,83 | 73 |
2 x 16 | rm | 17,2 | 550 | 1000 | 110 | 1,15 | 98 |